Rubi’s Smart Business Park Adventures · PARK · Season 1: How Things Connect · Episode 02. Morgan wants leak status and temperature in the building’s existing management system. The crew keeps a working temperature monitor, connects it to the LG5120 using Modbus RTU over a short RS-485 link, checks both the wired reading and the existing LoRaWAN leak report, then maps two verified Tags to BACnet/IP and checks the BMS readback.

Morgan asks for leak status and temperature in the existing BMS; Maya checks BACnet/IP support, and the crew considers keeping a working temperature monitor.
Story page 1 of 8 · Existing BMS, existing instrument
Rubi checks the temperature monitor manual for Modbus RTU over RS-485; Leo checks the unused port, settings and register map.
Story page 2 of 8 · Check the model and data source
The connection plan combines the plant-room LoRaWAN leak sensor LEAK07 and a short RS-485 link from temperature monitor T01 on the same LG5120, then shares selected data with the existing BMS over BACnet/IP on the existing LAN.
Story page 3 of 8 · One gateway, two sources
Leo connects temperature monitor T01 to the gateway’s RS-485 port, configures the temperature point and prepares to check the reading.
Story page 4 of 8 · Connect and configure the temperature point
The gateway temperature of 21.7°C matches the instrument, and the previously installed LoRaWAN leak sensor LEAK07 sends a fresh Dry report.
Story page 5 of 8 · Check both data sources
Leo maps checked temperature and leak Tags to two read-only BACnet/IP objects: Analog Input AI:1 and Binary Input BI:2, with 0 = Dry and 1 = Wet.
Story page 6 of 8 · Map selected Tags to BACnet/IP
The temperature rises to 21.8°C at the instrument and the existing BMS shows the matching temperature together with the leak sensor’s Dry state.
Story page 7 of 8 · Verify readback in the existing BMS
Morgan confirms both points are visible in the existing system while the instrument stays, then asks how to choose equipment for the next job.
Story page 8 of 8 · Keep the system. Add useful data.
Field Notes explains RS-485, Modbus RTU, Tags and BACnet/IP, using the temperature Analog Input and leak Binary Input as examples.
Field Notes · From readings to the BMS
Text version

Story page 1 of 8 · Existing BMS, existing instrument

FIELD CREW

How Things Connect · S1E02 · 01/08

Operations office · existing BMS

Morgan: Can our existing building system show the leak status and temperature?

Maya: I’ve checked. It can read BACnet/IP.

Temperature monitor

T01 · Comms room

Morgan: This instrument still works. Can we keep it?

EXISTING BMS

Building management

system

Building A

21.7

°C

Wireless Meets Wired · 01

Story page 2 of 8 · Check the model and data source

FIELD CREW

How Things Connect · S1E02 · 02/08

Check the model and the data source

Rubi: The manual says Modbus RTU over RS-485.

Comms room · inspect first

Leo: The port is unused. I’ve checked the settings and register map.

E2C FACILITY

Existing source

LEAK07

T01

Manual

CURRENT SETUP

Model matched

Settings checked

21.7

°C

21.7

°C

Wireless Meets Wired · 02

Story page 3 of 8 · One gateway, two sources

FIELD CREW

How Things Connect · S1E02 · 03/08

Comms room

Leo: We can connect this instrument to the same gateway with a short RS-485 cable.

Existing

LoRaWAN sensor

LEAK07

21.7

°C

OUR CONNECTION PLAN

Leak sensor

LEAK07 · Plant room

LoRaWAN

Temperature

monitor

T01 · Comms room

RS-485

Modbus RTU

LG5120

Comms room

Collect data

Share with the BMS

BACnet/IP

Existing LAN

Existing

BMS

T01

LG5120

Wireless Meets Wired · 03

Story page 4 of 8 · Connect and configure the temperature point

FIELD CREW

How Things Connect · S1E02 · 04/08

Connect T01 to LG5120 RS-485 channel 1

Configure and publish

Leo: The temperature point is ready. Let’s check the reading.

E2C FACILITY

T01 · Modbus RTU

Temperature · °C

Published · Read only

21.7

°C

21.7

°C

RS-485 data link

T01 → LG5120 · RS-485 channel 1

T01 data

LG5120

Data +

Data −

Signal GND

A1

B1

GND1

Check the signal labels in both manuals.

Wireless Meets Wired · 04

Story page 5 of 8 · Check both data sources

FIELD CREW

How Things Connect · S1E02 · 05/08

Compare the two readings

Leo: The gateway reads 21.7°C, just like the instrument.

Recheck the LoRaWAN leak sensor

Rubi: The leak sensor we installed earlier has sent a fresh Dry report.

T01

21.7°C

Updated 11:05:10

LEAK07

LoRaWAN leak sensor

Dry (0)

Plant room

Received 11:05:12

21.7

°C

21.7

°C

LEAK07 · Plant room

Installed earlier

Wireless Meets Wired · 05

Story page 6 of 8 · Map selected Tags to BACnet/IP

FIELD CREW

How Things Connect · S1E02 · 06/08

Choose the data for the BMS

Leo: I’ll map these checked Tags for the BMS.

Rubi: A Tag is one data point, like temperature.

E2C FACILITY

SELECTED TAGS

CommsRoom_Temp

Temperature · °C

Basement_Leak · 0/1

21.7

°C

BACnet/IP · TWO READ-ONLY POINTS

Checked Tag / source

BACnet object

CommsRoom_Temp

T01 · Comms room

21.7°C

AI:1

Analog Input

Temperature · °C

Read only

Basement_Leak

LEAK07 · Plant room

0 = Dry · 1 = Wet

BI:2

Binary Input

Leak · Dry / Wet

Read only

Only these two points are shared.

Existing LAN → Existing BMS

Wireless Meets Wired · 06

Story page 7 of 8 · Verify readback in the existing BMS

FIELD CREW

How Things Connect · S1E02 · 07/08

A moment later · comms room

Leo: It’s now 21.8°C here.

BMS readback · example view

Maya: Both points are linked. The BMS shows 21.8°C and Dry.

21.8

°C

EXISTING BMS

BACnet/IP

T01 · AI:1

21.8°C

LEAK07 · BI:2

Dry

Wireless Meets Wired · 07

Story page 8 of 8 · Keep the system. Add useful data.

FIELD CREW

How Things Connect · S1E02 · 08/08

Pilot result · existing BMS

Morgan: Both points, in our existing system. And the instrument stays.

EXISTING BMS

Temperature

21.8°C

Leak · Dry

After the check

Morgan: Can we see where our electricity goes, too?

Rubi: Let’s check what the meters can tell us.

BMS

Wireless Meets Wired · 08

Field Notes · From readings to the BMS

FIELD NOTES

How Things Connect · S1E02

From readings

to the BMS

RS-485 · the connection

Carries data signals along the cable between the instrument and gateway.

Modbus RTU · the requests

The gateway asks for a reading; the instrument replies. Its register map tells the gateway where to read.

Tag · one data point

One named data point, such as a temperature reading or a leak state.

BACnet/IP · into the BMS

The gateway makes selected readings available as BACnet objects for the existing BMS to read.

This example

AI:1 · Temperature

Comms room · °C

BI:2 · Leak state

Plant room · Dry / Wet

BACnet object types:

AI = Analog Input

Numeric reading

BI = Binary Input

Two-state status

Two read-only points.

Collect → Check → Map

→ Read in the BMS

FIELD CREW — by Robustel

Fictional story. BMS screens illustrate a separately configured receiving system.